500-9041 v4.1
Welcome Report
Control
Admin Sys Config Tech-Ref
57
___________________________________________
Common Commands--All Items
(After right-clicking the item)
------------------------------------------------------------------------
-
Resolve
(when alarms present)
:
Sets the
event/monitoring window to show only the
present alarms for the selected area or device;
-
Resolve and Show all Events for This Item
(when alarms present)
:
Sets the event/monitoring
window to show all alarms and events for the
selected area or device;
To return the Event/Monitoring Window to Its Previous
State: Click
[Return to Previous Filter]
at the
bottom of the window.
-
Switch to Control & Status screen for this
Item:
This jumps you to the form-based
"Control & Status" screen for the selected item.
___________________________________________
Area Commands
(After right-clicking an Area)
Also See: "Common Commands", previous/above.
-------------------------------------------------------------------------
-
Off / Stay / On:
These selections allow
manually arming or disarming the area (i.e.,
setting the arming level);
Tip:
If any input points (sensors) are presently tripped
or bypassed, you will be guided though the steps to
deal with this first (bypass / acknowledge).
-
Silence
(when an item is in 'alarm')
:
This shuts off
the sounding of present alarms (i.e., shuts off
the system siren output, and LCD keypad
sonalerts).
-
Worklate:
This allows adjusting the area's
scheduled closing time in increments of 30
minutes.
-
Lock All Doors in this Area:
This locks all
doors with at least one reader associated with
the specific area;
-
Unlock all Doors in this Area:
This unlocks all
doors with at least one reader associated with
the specific area;
___________________________________________
Door Commands
(After right-clicking a Door)
Also See: "Common Commands", previous/above.
-------------------------------------------------------------------------
-
Lock:
This locks (re-locks) the specific door.
-
Unlock:
This unlocks the specific door.
-
Momentary Normal Unlock:
This unlocks the
door for a duration equal to the standard "unlock
duration". This is the same as someone gaining
entry with an access card or token.
-
Momentary Extended Unlock:
This unlocks
the door for a duration equal to the "extended
unlock duration". This is the same as a user
who is set for "extended unlock/challenged"
gaining entry with an access card or token.
-
Pending Unlock:
This is an unlock command
that waits for one person to enter the facility at
the specific door.
___________________________________________
Input-Point Commands
(After right-clicking a Sensor)
Also See: "Common Commands", previous/above.
-------------------------------------------------------------------------
-
Bypass / Remove Bypass:
"Bypass" allows
arming an area with a tripped or faulty input
point (sensor). "Remove Bypass" allows
monitoring the input point again (for a sensor
that is "OK").
___________________________________________
Elevator Commands
(After right-clicking an Elevator)
Also See: "Common Commands", previous/above.
-------------------------------------------------------------------------
-
Secure / Desecure:
This allows applying or
removing controlled-access for all floors as
accessed from the specific elevator (lift).
(Secure: An access card or token provides access to
specific floors;
Desecure: Anyone can access any floor without a
card or token.
Controlling a Floor (as accessed from all cabs): Refer
to "Checking Status or Controlling Floors".