22-9058 v2.1
Welcome
PCPanel IP
Cent. Mon. with IP
Ref. Topics
7
2.2 Component Wiring for
PCPanel with IP
2.2.1 Wiring Concept (PCPanel with IP)
LAN/WAN
ISM/AFx
Main
Panel
Director Software
10BaseT / RJ45
Up to 30 panels
per connection
More
Panels
Pwr Req'd
12V, 250mA
To sensors,
modules,
etc.
IP
Interface
Module
)
Single-panel connections needed for
panel-initiated comms (details in 2.1.1).
To sensors,
modules, etc.
(single PC, or client/server)
RS485 (24AWG, 4-wires,
shielded) Tested to 300m/1000ft
(Optional)
(
Shared with SIP
reporting, if applicable.
(wiring is separate)
2-wire power cable
required if power
supply is separate.
∗
Never use reader
cable for this!
Use 24 AWG, 4 conductor comms cable FT4 P/N 120-3401, FT6 P/N 120-3405. Add a 2
nd
cable of the same
type for cable runs over 4 wires. Use 18AWG power cable FT4 P/N 120-3400, FT6 P/N 120-3404 for power
supply connections.
2.2.2 Wiring Details (PCPanel with IP)
21
3
21
TB2
Main Panel
Motherboard
TB2
TB16
0V
+12 v
TB
Locations
Yellow wire
Green wire
∗
Shared w/ SIP reporting (if applicable)
Main Panel
Module Bus
(assoc. with
any ext. P/S)
1234
298-8522
(3A)
TB10 - TB13
'B'
Connector
IP Interface Module
RJ45
To Network
+12V
Data A
Data B
0V
Other wires/connectors: used
ONLY with SIP reporting (for
SIP wiring, see section 3.3)
21
3
∗
If separate P/S used instead, IP board TB2-3 (Dir Ground) must be
shorted to related motherboard TB16-3 (0V).
See Sect. 4.2, Figure 5.
If P/S is interfaced with Module Bus remotely to help power
other devices (+12V connection), install isolating diodes (3
A; P/N: 298-8522) at the panel (Module Bus +12, with band
facing away from panel connection).
Power Considerations
During Configuration: 12V power and a LAN (not WAN)
connection is required when configuring the IP Module.
(Use RS-485, shielded
cable if IP board is
remotely located.)
A485
1
0V
B485
32
TB16
To TB16 on
2nd panel
(RS-485, shielded)
TB16
IP Module
Main Panel
Motherboard
TB2
Control Box Mounting IP Module
board wires are made purposely long to
allow running them around main panel
motherboard to avoid electrical
interference across the motherboard.
Prewired terminal blocks
for connections on
motherboard are
supplied.
(+)
(-)
Battery Terminals
this end.
Black wire
Red wire
TB2
A485
1
0V
B485
32
D
i
r
G
r
o
u
n
d
D
i
r
R
S
4
8
5
B
D
i
r
R
S
4
8
5
A
(if applicable)
132
To TB16 on
next panel etc.
First Panel
For more detail on power and grounding requirements, refer to sections 1.4 and 1.5.
LED Reference: For details on the
operation of the on-board LED’s, refer to
the hardware reference, Sect. 4.2.
Kommentare zu diesen Handbüchern